Reg. 354

Screwed on Flanges

Where flanges are secured by screwing the screw thread on the pipes and in the flanges shall be arranged to end at a point just inside the back of boss of the flange. After the flange has been screwed on, the pipe shall be expanded into the flange by a roller expander. Such screwed and expanded flanges may be used for steam for a maximum working pressure of 31.5 kg/cm² (450 lbs./sq. in) and a maximum temperature of 399°C (750°F) and for feed for a maximum pressure of 42 kg/cm² (600 lbs./sq. in.).
 