Reg. 321, Reg. 322, Reg. 323, Reg. 324, Reg. 325, Reg. 326

Drains

 
A drain cock or valve with a suitable discharge pipe shall be fitted to each water gauge.


Reg. 322

Protectors

Where tubular glass water gauges are fitted, substantial protectors shall be provided. The glass shall be suitable treated to prevent splintering.


Reg. 323

Glass size

Tubular water gauge glasses shall be not less than ½ inch and not more than 3/4 inch outside diameter.



Reg. 324

Safety Devices


Water gauge glass mountings shall be fitted with self-closing devices in the bottom arm and it is recommended that a similar device should be fitted in the top arm.


Reg. 325

Gauge columns


Where the gauges are mounted on a column there shall be no connecting passage between the top and bottom arms of the column unless valves or cocks are fitted between the columns and the boiler.


Reg. 326

Isolating Cocks


Where isolating cocks or valves connecting water gauge pipes to the boiler are fitted, they shall be not less than 1 inch bore and of the bolted cover type with separate packing gland.
 
Back   Top
Message from Chairman of Central Boilers Board About Central Boiler Board History of Indian Boiler Regulations Foreword Contents Chapter Wise Contents Regulation Wise List of Amendments
Indian Boilers Act 1923 Ibr Forms Home Search Help Contact Us