Message from
Chairman of Central Boilers Board


About Central Boilers
Board


History of Indian Boiler Regulations

Foreword

Contents Chapter
Wise


Contents Regulation
Wise


List of Amendments

Indian Boilers
Act 1923


Ibr Forms

Home

Search

Help

Contact Us

Reg. 198, Reg. 199, Reg. 200
FLAT PLATES


Circular flat ends of drums, etc., supported only at edges

a) For these ends C in Equation 35 shall be taken as 140 when the plates are not exposed to flame, and 122.5 when they are exposed to flame. In this case the circle D shall pass through the centres of rivets or bolt securing the end be less than 4 times, the thickness of the end plate but in no case less curvature.
b) Where flanged the inside radius of curvature at the flange shall not be less than 4 times, the thickness of the end plate but in no case less than 2-1/2".



Reg. 199
FLAT PLATES


Bar or bulb stiffened end plates and smoke-box tube plates of Loco-type boilers

Where such plates instead of being supported by stays are stiffened in the steam space by substantial tee or angle bars securely riveted to the plate and extending across the plate to within the margin allowed by the Equation(35) or where such plates are formed with a deep bulb extending across the plate to well within the margin allowed, for the support thus given.

C shall be taken as equal to 80 and 70 for plates not exposed, and exposed to flame respectively. The margin or pitch for such stiffening shall be measured from the centre line of rivets or commencement of curvature of bulb provided it is not more than 2 inches from the centre line of bulb.

For the flat plate above the stiffener or bulb, C shall be taken as the mean of the values appropriate for the points of support.


Reg. 200
FLAT PLATES


Flat plate margins

The amount of support in relief of stays which may be credited to the sides of shells, furnaces, uptakes, fireholes and foundries rings to which flat plates are attached shall not exceed that found by the following formula :

 

Width of margin in inches = C ( t - 1 ) Eqn.(37)
         (W. P)1/2

where
t = thickness is 32nds of an inch

W. P. = Working pressure in lbs. per sq. inch.

C = 3.47 for plates exposed in flame.

C = 3.70 for plates not exposed to flame.

Where the plates are flanged the margin shall be measured from the commencement of curvature or from a line 2-1/2 times the thickness of the plate distant from the side of the flange next to the inner radius of the corner whichever is the less. In other cases, the margin shall be measured from the centre line of rivets in the nearest row of the seam by which the flat plate is attached.

Doubling plates shall cover the area supported between the stays and extend beyond the stays so that the centre of the rivets securing the doubling plate to the end plate shall be at least half the distance from the outermost stays to the nearest substantial point of support.

Where flat end plates are flanged for connection to the shell the inside radius of flanging shall be not less than 1.75 times the plate thickness with a minimum of 1-1/2 inches.
 
Back   Top