Reg. 159
STAND PIPES, PADS ETC.

 

Attachment of Mountings

a) Mountings may be attached directly to any shell or end plate where the plate is of sufficient thickness to allow a suitable surface to be obtained for the attachment of the boiler mountings.
b) The minimum thickness at the hole in the shell or end plate shall be not less than the thickness required for the maximum permissible working pressure considering the plate as being unpierced.
c) Where the boiler mountings are secured by studs, the studs shall have a full thread holding in the plate for at least one diameter. If the stud holes penetrate the whole thickness of the plate, the stud shall be screwed right through the plate and be fitted with a nut inside having a thickness equal to the diameter of the stud. Where bolts are used for securing mountings they shall be screwed right through the plate with their heads inside the shell or end plate.
 