Reg. 266 d, Reg. 266 e, Reg. 266 f, Reg. 266 g, Reg. 266 h,
Reg. 266 i
Removal of Defects |
| Defects shall be
cut out by chipping or machining or by burning out by
the "Air Arc Weld Process. |
Reg. 266 e
Examination before Re-welding
|
Where a defective part has been cut out, the Inspecting
Authority shall be entitled to make an examination before
re-welding.
|
Reg. 266 f
Process used for Repairs
|
Only metallic arc welding shall be used for repairs.
|
Reg. 266 g
Radiographical Examination after Repairs
|
All
repaired areas shall be subjected to radiographic or
radioscopic examination by the approved techniques.
|
Reg. 266 h
Specimen Representing Repairs
|
The Inspecting Authority shall be entitled to call
for specimens representing any welded repair, for the
purpose of examination and test.
|
Reg. 266 i
Diagram of Welded Repairs
|
On completion of all welded repairs the manufacturers
shall, if requested, supply for record purposes a detailed
diagram showing the position, length, depth and width
of all such repairs.
|
|
|